THERMAL OVERLOAD RELAY - TZ
TERMIČKA ZAŠTITA
Prevents overheating of motor windings. Can be used with motors that have built-in temperature-dependent resistors (PTC) in windings. Choice of automatic or manual reset.
Basic features:
-standard supply voltage: 230Vac; 24Vac/dc
-consumption: 2VA
-cut off  threshold: when the PTC resistance reaches 3000ohm  (+ / -10%)
-restart: when resistance drops to 2000ohm (+ / -10%)
-contact rating: 5A/220Vac
-operating temperature range: -10 / +55 C


TERMIČKA ZAŠTITA MOTORA
LEVEL SWITCH - RZP
ZAŠTITA PUMPE OD RADA NA SUVO

It is used to detect the presence of conductive liquids in metal or tanks of insulating material. It can be used to automatically refill the reservoir or to protect the pump from dry running. With jumper 5-6 on the front panel you can choose whether the relay will be on when the liquid level reaches the probe S1 (pump protection) or to be off when S1 is reached (filling a tank).
Basic features:
power supply: 230Vac
consumption: 2VA
contact rating: 5A/230Vac
mounting: rail 35mm

RELE ZAŠTITE PUMPE
UNDERVOLTAGE/OVERVOLTAGE RELAY - NR
PODNAPONSKI PRENAPONSKI RELE

Detection of too high or too low line voltage. Control voltage also serves to power up relay.

Basic features:
rated voltage: 230Vac (others on request)
under voltage threshold: adjustable from 160-220Vac - 10V hysteresis
over voltage threshold: adjustable from 220-260VAC - 5V hysteresis
consumption: 4VA
contact type and rating: two changeover contacts 5A/250Vac


PODNAPONSKI PRENAPONSKI RELE
THREE PHASE UNDERVOLTAGE/OVERVOLTAGE RELAY NR3
TROFAZNI PODNAPONSKI PRENAPONSKI RELE

Independently adjustable threshold:

-undervoltage-160...220Vac 
-overvoltage -220...260Vac
 

 
PHASE SYMETRY AND UNDERVOLTAGE CONTROL - NF03

Main purpose is protection of three-phase motors and other consumers from line voltage failure and asymmetry. Control voltage also serves to power up relay. 
Designed to operate in networks with grounded neutral point. 

Basic features:
Operating voltage: 3X230/400Vac
Contact rating: 5A/230Vac

Adjustable:
-asymmetry 5-30% 
-under voltage: 160 .. 220V
-Standard: automatic reset
-Option: manual reset


 

 
PHASE SYMETRY AND UNDERVOLTAGE CONTROL WITH TIME DELAY - NFT03
RELE ASIMETRIJE I PRISUSTVA FAZA
Adjustable:
-asymmetry 5-30% 
-time delay 0-10s 
-automatic reset
-option: manual reset

Fixed:
-under voltage:175V

 

 
PHASE SEQUENCE, SYMETRY AND UNDERVOLTAGE CONTROL - NF04
RELE REDOSLEDA ASIMETRIJE I PRISUSTVA FAZA
Detection of the correct phase sequence

Adjustable:
-asymmetry 5-30% 
-under voltage: 160... 220Vac
-standard: automatic reset
-option: manual reset:

 

 
PHASE SEQUENCE, SYMETRY AND UNDERVOLTAGE CONTROL WITH TIME DELAY - NFT04
RELE REDOSLEDA, ASIMETRIJE I PODNAPONA SA VREMENSKOM ZADRŠKOM

Detection of the correct phase sequence

Adjustable:
-asymmetry 5-30% 
-time delay 0-10s 
-automatic reset
-option: manual reset

Fixed:
-under voltage: 175V

 
RELAY FOR POWER FACTOR CORECTION - COS FI

RELE ZA KOREKCIJU FAKTORA SNAGE

 

Measure angle between phase voltage and current and has the ability to correct power factor in three steps by adding capacitor banks. A simple solution for small business sites and consumers who have no reactive power variations in a wide range.

 

 
DIMENSIONAL DRAWING
dimenziona skica

A=22.5mm

NR3,NF03,NF04,NFT03,NFT04, TZ

A=37mm...RZP,COS FI

 

NR

dimenziona skica
In order to rationalize production and continuous improvement of product quality  changes are possible in the appearance and characteristics of actual devices compared to this catalog.